Address : Perkantoran Kedoya Elok Plaza Blok DC 47
    JL. Panjang, Jakarta 11520, Indonesia
Phone : (+62-21) 5806180
Fax : (+62-21) 5809185
E-mail : pt_msc@cbn.net.id
   
Current Range: 16 A
1:1

16 A

Multi Switch ATS provides installations with power supply continuity. Its operating principle ensures higher reliability than a single UPS , (with or without its own internal bypass).

  1. Characteristics
  2. Documents
  3. Technical Specifications

Operating principle
Multi Switch ATS provides direct distribution of eight 10 A IEC consumers or one 16 A IEC consumer in a system with two input power lines (two mains inputs, or two UPS ).
Multi Switch ATS is able to connect to either of the two input power lines, whilst simultaneously monitoring the power uptake.

Protection against load faults
If one of the loads fails (e.g. short circuit), Multi Switch ATS disconnects the group of sockets where the load is connected, thus preventing other loads from being switched off (i.e. in the event of poor selectivity of the protection devices).

Protection against power supply faults
If one of the two power sources falls outside tolerance levels, Multi Switch ATS will transfer the consumers to the second power source (switching is instantaneous if the two sources are in phase).

Features

  • Full protection for consumers against mains and load failures
  • Versatile to use: Multi Switch ATS can be powered with 2 different power supplies (2 UPS even of different sizes/types)
  • 19” cabinet installation
  • Display panel
  • Can be connected to PowerNetGuard supervision software
  • No signal connection between the Multi Switch ATS and the power sources or consumers is necessary
  • Compatible with PowerShield³ software
  • Slot for communications boards.
 
ModelsMTA 16A
INPUT
Voltage 180÷276 Vac
Frequency 50/60 Hz
ENVIRONMENTAL
Altitude max 3000 m
Color Dark grey RAL 5004
Communication DB9 with RS232 and USB ports, slot for communications interface, relay contact port
Protection rating IP20
Protections Overcurrent - overvoltage - undervoltage - protection against energy back-feed
Noise < 35 dBA
Operating temperature 0 °C / +40 °C
Relative humidity <95% non-condensing
Output sockets 4+4 IEC-320 C13 (10 A) + 1 IEC-320 C19 (16 A)
DATA
Weight 6 Kg
Dimensions (h w d) 1U x 19” x 330 mm
next
prev